| Model |
3W3-10k 3W3-15k
3W3-20k 3W3-30k 3W3-40k |
| Output capacity |
10KVA
15KVA
20KVA 30KVA 40KVA |
| Input |
Voltage Frequency range Power factor |
380VAC±20%(3φ+N)(at normal load) 45-65
Hz 0.95 |
| Output |
Voltage Setting range Crest factor Wave form Distortion with liner load Stability voltage
at steady state Stability voltage at transient state Frequency Frequency stability without
synchronization Frequency stability with
synchronization Effective Overload |
380 VAC 3φ+N 346-415 VAC (on the control
panel) 3:1 sinewave 2.5% ±1%
±4%
50/60 Hz the same of input ±0.05%
frequency is same as bypass
92% 110%/125%/150% nominal voltage 300/30/3
s |
| Battery |
Type VDC Widing |
sealed lead-acid maintenance free 192+192
VDC / 288+288VDC | 288+288VDC Different battery combinations |
| Bypass |
Type Voltage
Input frequency range Overload capacity per 1
min. |
STATIC+manual per maintenance operation 380VAC±15%(±10%~±20%) 3Ø+N (on the control panel) ±2%(+1%~+5%)(on the control panel) 200%
|
| Transfer time |
AC fault UPS fault |
0ms < 2ms |
| System |
Remote signaling
Remote command Computer interface Operating temperature Relative humidity Max operating altitude
Cooling Noise level at 1 m. dBA Protection level Applicable standards
Option
Dimensions(WxDxH) Weight(UPS only) |
3 tension f.e.contacts(mains failure,bypass,prealarm
end discharge battery) EPO and Bypass Standard RS232x2 0-40°C 95%
without condensation 1000m at rated power An(-1% An for
each 100m over i 1000m)-max 4000m force venational(fan
speed fungating of load) < 56dBA IP20 Safety EN50091-101,Electromagnetic
compellability EMC EN 50091-2 liv.A Insulation
transforms-harmonic suppression filter-parallelism kit up to six
units 505x720x1135mm
|
505x795x1210 mm 100kg
114kg
120kg 126kg
132kg |