IEAS Electronics Technology Co.,Ltd
|
|
| |
| IEAS UPS |
|
 |
High Frequency On Line 3 /1 10kva 15kva 20kva UPS |
|
|
|

|

|
Click to enlarge image
|
Model Number |
3HF10K(S) 3HF15K(S) 3HF20K(S) |
|
Model |
3HF10KS |
3HF15KS |
3HF20KS |
|
Rated Power |
VA/W |
10kVA/7kW |
15kVA/10.5kW |
20kVA/14kW |
|
Input |
Nominal Voltage |
380VAC |
|
Voltage Range |
304 ~ 478VAC |
|
Phase |
3 phase (4 wires plus ground) |
|
Frequency Range |
46 ~ 54Hz |
|
Power Factor |
0.95 |
|
Connection |
Hard wired |
|
Output |
Voltage |
220VAC/230VAC/240VAC ± 2% |
|
Frequency |
Sync with input frequency. If input frequency is out the
range of 46Hz ?54Hz(57Hz ?63Hz), the output frequency is 50Hz(60Hz) ?
(1±0.1%)Hz.
50Hz or 60Hz?1±0.1%)Hz 〔 battery mode 〕 |
|
Waveform |
Sine Wave |
|
Power factor |
0.7 |
|
Voltage Distortion |
?2% under linear load |
|
Overload Capability |
105% ~ 130% for 10 min., ?130% for 1 min. |
|
Current Crest Ratio |
3:1 max. |
|
Battery |
Type |
Sealed, Maintenance free, Lead-Acid |
|
Nominal DC Voltage |
240VDC |
|
Back-up time (full load) |
Depends on the capacity of the external battery capacity
|
|
Connection |
External Battery Socket |
Hardwired |
|
Transfer time |
0 ms |
|
LED indicators |
Status |
Load level/Battery level, Battery , Utility power, Inverter,
Bypass, Overload, Fault |
|
Audible alarm |
Bypass |
Alarm beeps every two minutes |
|
Battery discharge |
Alarm beeps every four seconds, every second if battery low
|
|
Overload |
Alarm beeps two for every second |
|
Fault |
Alarm beeps continuously |
|
Acoustic noise |
At 1 meter distance |
?55 dBA |
?60 dBA |
|
Communications |
DB-9 Port |
RS232 serial interface |
|
Intelligent Slot |
Options: WebPower, As400 or WinPower CMC |
|
Environmental |
Operating temperature |
0 ~ 40 ° C |
|
Operating humidity |
20% ~ 90% non-condensing |
|
Weight |
Net (kg) |
92 |
95 |
|
Dimensions |
W x D x H (mm) |
340 * 640 * 980
|
|
|
|
|
| |
|
|
|