IEAS Electronics Technology Co.,Ltd
|
|
| |
|
|
|
|

|

|
Click to enlarge image
|
Model Number |
HF1KVA |
|
Model |
HF1K |
HF2K |
HF3K |
|
Rated Power |
VA/W |
1kVA / 0.7kW |
2kVA / 1.4kW |
3kVA / 2.1kW |
|
Input |
Nominal Voltage |
220VAC |
|
Voltage Range |
120 ~ 300VAC |
|
Frequency Range |
46~54Hz(default), user adjustable within 40~60Hz
|
|
Power Factor |
0.97 |
|
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
|
Output |
Voltage |
220VAC/230VAC/240VAC ± 2% |
|
Frequency |
Sync with input frequency. If input frequency is out
the range of 46Hz ?54Hz(57Hz ?63Hz), the output frequency is
50Hz(60Hz) ?(1±0.2%)Hz.
50Hz or 60Hz?1±0.2%)Hz〔battery mode〕 |
|
Waveform |
Sine Wave |
|
Distortion |
THD <3% ( linear load )、 THD
<5% ( non-linear load ) |
|
Overload Capability |
108%~150% for 30 sec., ?150% for 300 ms |
|
Current Crest Ratio |
3:1 |
|
Connections |
Click here to check pictrues
|
|
Battery |
Type |
Sealed, Maintenance free, Lead-Acid (Panasonic)
|
|
Quantity |
3 pieces |
8 pieces |
|
Back-up Time (Full load) |
5 min |
9 min |
5 min |
|
Recharge Time ? |
5 hrs to 90% of capacity after full load discharge
|
|
Bypass
|
Automatic Transfer |
on overload and UPS failure |
|
Before UPS Power-on |
Default ?O? user adjustable to ?ES? |
|
Voltage Range |
80~264VAC (Default), user adjustable within
80~286VAC |
|
Transfer Time |
0 ms; less than 4 ms from inverter to bypass and
vice versa |
|
LED OR LCD |
Status |
Load level / Battery level, Battery , Utility Power,
Inverter, Bypass, Overload, Fault |
|
Audible Alarm |
Bypass, On battery mode, Battery low, Overload,
Fault |
|
Acoustic Noise |
At 1 meter distance |
45 dB |
50 dB |
|
Communications |
DB-9 Port |
RS-232 Serial Interface |
|
Intelligent Slot ? |
Options: WebPower, AS400 Card or WinPower CMC
|
|
Network Surge Protection |
RJ45 I/O port available for network or Fax/Modem
|
|
Environmental |
Operating Temperature |
0 ~ 40 ° C |
|
Operating Humidity |
20 ~ 90% non-condensing |
|
Weight |
Net (Kg) |
13 |
33 |
34 |
|
Dimensions |
W x D x H (mm) |
145 x 405 x 220 |
195 x 455 x 330 |
|
|
Model |
HF1KS |
HF2KS |
HF3KS |
|
Rated Power |
VA/W |
1kVA / 0.7kW |
2kVA / 1.4kW |
3kVA / 2.1kW |
|
Input |
Nominal Voltage |
220VAC |
|
Voltage Range |
120~ 300VAC |
|
Frequency Range |
50Hz ± 5%(default), user adjustable within 40~60Hz
|
|
Power Factor |
0.98 |
|
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
|
Output |
Voltage |
220VAC ± 3% |
|
Frequency |
Sync with input frequency. If input frequency is out
the range of 46Hz ?54Hz(57Hz ?63Hz), the output frequency is
50Hz(60Hz) ?(1±0.2%)Hz.
50Hz or 60Hz?1±0.2%)Hz〔battery mode〕 |
|
Waveform |
Sine Wave |
|
Distortion |
THD <3% ( linear load )、
THD <5% ( non-linear load ) |
|
Overload Capability |
108% ~ 150% for 30 sec., ?150% for 300 ms
|
|
Current Crest Ratio |
3:1 |
|
Connections |
different connections according to
different standard |
|
Battery
|
Type |
Sealed, Maintenance free, Lead-Acid |
|
Nominal DC Voltage |
36VDC |
96VDC |
|
Back-up Time |
Depends on the capacity of the external battery bank
|
|
Connection |
External Battery Socket |
|
Bypass
|
Automatic Transfer |
On overload and UPS failure |
|
Before UPS Power-on |
Default ?O? user adjustable to ?ES? |
|
Voltage Range |
80 ~ 264VAC (Default), user adjustable within 80 ~
286VAC |
|
Transfer Time |
0 ms; less than 4 ms from inverter to bypass and
vice versa |
|
LED OR LCD |
Status |
Load level / Battery level, Battery , Utility Power,
Inverter, Bypass, Overload, Fault |
|
Audible Alarm |
Bypass, On battery mode, Battery low, Overload,
Fault |
|
Acoustic Noise |
At 1 meter distance |
45 dB |
50 dB |
|
Communications |
DB-9 Port |
RS-232 Serial Interface |
|
Intelligent Slot |
Options: WebPower, AS400 Card or WinPower CMC
|
|
Network Surge Protection |
RJ45 I/O port available for 10 base-T network or
Fax/Modem |
|
Environmental |
Operating Temperature |
0 ~ 40 ° C |
|
Operating Humidity |
20 ~ 90% non-condensing |
|
Weight |
Net (Kg) |
7 |
18 |
19 |
|
Dimensions |
W x D x H (mm) |
145 x 400 x 220 |
192 x 460 x 348
| |
|
|
|
|
| |
|
|
|