High Frequency Rack Mount 1kva 1.5kva 2kva 3kva 6kva UPS

Inquire now

High Frequency Rack Mount 1kva 1.5kva 2kva 3kva 6kva UPS

Click to enlarge image

 Model Number HF19-1KVA HF19-1.5KVA HF19-2KVA HF19-3KVA 6KVA

Model

HF 19- 1K

HF 19- 1.5K

HF 19- 2K

HF 19- 3K

HF 19- 6K

Rated Power

VA/W

1kVA/ 0.7kW

1.5kVA/ 0.7kW

2kVA / 1.4kW

3kVA / 2.1kW

6kVA/4.2kW

Input

Nominal Voltage

220VAC

Voltage Range

120 ~ 300VAC

176 ~ 276VAC

Frequency Range

46 ~ 54Hz(default), user adjustable within 40~60Hz

46 ~ 54Hz

Power Factor

0.98

0.98

Connection

IEC320-10A inlet

IEC320-16A inlet

Terminal Block

Output

Voltage

220VAC ± 2%

220VAC ± 1%

Frequency

Sync with input frequency. If input frequency is out the range of 46Hz ?54Hz(57Hz ?63Hz), the output frequency is 50Hz(60Hz) ? (1±0.2%)Hz.

50Hz or 60Hz?1±0.2%)Hz 〔 battery mode 〕

Sync with input frequency. If input frequency is out the range of 46Hz ?54Hz(57Hz ?63Hz), the output frequency is 50Hz(60Hz) ?(1±0.2%)Hz.

50Hz or 60Hz?1±0.2%)Hz 〔 battery mode 〕

Waveform

Sine Wave

Overload Capability

108%~150% for 30 sec., ?150% for 300 ms

105%~130% for 10 min., ?130% for 1 min.

Current Crest Ratio

3:1

Bypass

Automatic Transfer

on overload and UPS failure

Before UPS Power-on

Default ?O? user adjustable to ?ES?

Yes

Voltage Range  

80~264VAC (Default), user adjustable within 80~286VAC

176 ~ 261VAC

Output Connections

different connections according to different standard

Transfer Time

0 ms; less than 4 ms from inverter to bypass and vice versa

0 ms

LED indicators

Status

Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault

Audible Alarm

Bypass, On battery mode, Battery low, Overload, Fault

Communications

RS-232 Serial Interface

Intelligent Slot;
OPTIONS: WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC)

Network Surge Protection

RJ45 I/O port available for network or Fax/Modem

Environmental

Operating Temperature

0 ~ 40 ° C

Operating Humidity

20 ~ 90% non-condensing

Main Unit

Net Weight (Kg)

15.3

10.3

11.2

18.3

Dimensions (W x D x H) mm

482.6 x 450 x 88 (2U)

482.6 x 600 x 130 (3U)